nipom OAO
Low voltage electrical switchboard NKU Freecon
Electricity - electronics- electrotechnical > Energy: production and distribution > Switchgear
Electricity - electronics- electrotechnical > Energy: production and distribution > Switchgear
Designation
Low Voltage Electrical Switchboards “NKU” are designed to receive and distribute electric power (0.69 kV, 50 (60) Hz
three-phase alternative current) among consumers.
Application
It functions as:
- General switchboards and sub- switchboards, Automatic Transfer Switch (ATS) panels
- Aggregate panels of electro-technology installations control stations
- LV Switchgears of Packaged Transformer substations
- Utilities Switchboards for Electric Generating Stations, etc.
Functional Capabilities
- Electric installations power supply protection-ATS arrangement from electric power system (max. 2 lead-ins) and emergency power supply sources, in particular, from electric power system (max. 2 lead-ins) and diesel run power plan (max. 2 lead-ins)
- Control of power supply system parameters and status
- Local, remote and automatic control of power consumers
- Reception of control signals and signals generation of consumers status via wire and digital communication channels (Modbus, Profibus)
Construction Merits
“Freecon” Low Voltage Electrical Switchboard is a freely configurable system based on “F4” in-house / “NIPON” OJSC /
form factor — (for 6,300 A current, max.) and based on “SIVACON S8” licensed unified form factor — (for 7,000 A current,
max.) and “Logstrup” — (for 8,500 A currents, max.).
Low Voltage Electrical Switchboards are connected to Distribution Networks:
- By cables from below and top
- By buses / bus ducts from top, laterally
Consumers are connected to Low Voltage Electrical Switchboards:
- By cables from below and top
- By buses / bus ducts from top
Modifications:
- CT — single-side / double side maintenance sections with fixed equipment
- CM — single-side / double side maintenance sections with retractable / removable modules
Additional Options
- Link with High-Level Automatic Process Control Systems
- Digital controller for Relay Protection and Automatic Equipment and Automatic Transfer Switch (ATS)
- Modbus, Profibus Communications Protocols
- Electric power metering devices with digital data communication to Utility Metering System
- ATS based on microprocessor relay protection units and Programmable Logic Controllers (PLC)
- Microprocessor units for electric motors protection
- Electric equipment status control, event log keeping, data display on a Central Processing Module
Parameter name | Parameter values | Unit of measure |
---|---|---|
Equipment seismic load resistance as per MSK64 scale
|
9
x
x
|
grade
x
x
|
Grounding system type
|
TN-C, TN-C-S, TN-S
x
x
|
x
x
|
Rated permissible short time current of bus bars, Icw
|
100
x
x
|
kA
x
x
|
Rated shock current of bus bars, Ipk
|
200
x
x
|
kA
x
x
|
Rated Switchboard current
|
6300
x
x
|
A
x
x
|
Rated voltage
|
690
x
x
|
V
x
x
|
distribute electric power (0.69 kV, 50 (60) Hz three-phase alternative current) among consumers
Low voltage electrical switchboard NKU Freecon,Low voltage electrical switchboard,Low voltage,electrical switchboard,NKU Freecon,Freecon
* Indicates required field